EV-101DC Damper Interface Panel, 24V DC, 0.8A Output

£133.00 / £159.60 incl. VAT

The EV-101DC Damper Interface Panel provides reliable 24V DC power, monitoring and control for fail-safe and smoke control damper actuators. Featuring continuous status monitoring, clear visual indicators and an automatic self-test function, it helps simplify maintenance and verify dependable damper operation.

An optional hotbox enclosure extends fire survival to 300°C for 90 minutes.

Frequently Bought Together

damper control panel 24V DC + fire-smoke-damper-control-system + EV-101AC Damper Interface Panel, 230V AC, 1.25A Output + EV-101AC Damper Interface Panel, 230V AC, 1.25A Output with Hotbox
Price for all: £6,917.00

The EV-101DC Damper Interface Panel is a dedicated solution for powering and monitoring fail-safe and smoke control damper actuators. Designed for dependable system performance, it can operate as a standalone unit or integrate into an addressable damper control system, providing flexibility across natural ventilation, damper control, and smoke control applications.

Equipped with continuous monitoring, the panel provides real-time indication of damper position and operational status through clear visual indicators. A built-in self-test function automatically exercises the damper to verify correct operation and identify faults, helping to simplify maintenance and support reliable long-term performance.

The EV-101DC supports two operating configurations:

  • Standalone Mode – triggered directly by a connected smoke detector or fire alarm interface.
  • Addressable Mode – integrated with the EV-DCP-N damper control panel and operated in response to programmed cause-and-effect logic.

For resilience, the panel accepts an 85-253V AC input and includes a 24V DC back-up input. It provides a 24V DC, 0.8A output for connected damper actuators. The standard EV-101DC is housed in a compact IP66-rated ABS enclosure with a light grey RAL 7035 finish and weighs 0.9kg.

For applications requiring extended fire survival, the EV-101DC-HBV version includes an IP55-rated thermal Hotbox enclosure manufactured from FabBloc insulating material. The Hotbox provides fire survival at 300°C for 90 minutes, independently witnessed by Lloyd’s Register, and has a total weight of 5.6kg including the panel.

Additional highlights include:

  • Continuous damper position and status monitoring.
  • Automatic self-test functionality for operational verification and fault identification.
  • Clear visual status indicators.
  • 24V DC, 0.8A actuator output.
  • 24V DC back-up supply input.
  • Standalone or addressable system operation.
  • Compliance with BS EN 12101-10 and BS ISO 21927-9.

With intelligent monitoring, flexible system integration, and an optional fire-resilient Hotbox enclosure, the EV-101DC provides a dependable interface solution for supporting effective operation of fire and smoke control dampers.

Under the Construction Products Regulations (CPR) it is a legal requirement to use only certified products for smoke ventilation. For more information see Group SCS’ Technical Bulletin. It is the responsibility of the installer to ensure installations meet the relevant standards and that the installer has the appropriate competence to install or replace smoke ventilation products. We recommend installers hold an up-to-date IFC SDI 19 Smoke Control Systems certification to demonstrate compliance.

Weight 0.9 kg
Dimensions 180 × 90 × 182 mm
Enclosure

Panel only

Brand

SIMON PROtec

Conformity

BS EN 12101-10, BS ISO 21927-9

Cable Entries

8 no. M20, 1 no. M25/M32 knockouts

IP Rating

IP66

Max Current Load

24V DC, 0.8A

Voltage Output

24V DC, 0.8A

Voltage Input

85-253V AC, 0.4A

Operating Temperature

-5 to +70 °C ambient temperature

Finish

ABS plastic, RAL 7035 light grey

Dimensions

H:182mm x W:180mm x D:90mm

Product Weight

0.9Kg